- R.R.T. Rapid Readout Technology
- Simple touch screen operation with alphanumeric keyboard
- X-large display shows all combustion data values simultaneously
- Advanced communication and data storage capabilities
- Optional probes for a variety of applications
- Automatic cleanout pump for safe CO measurements
- Customer sensor exchange: saves time and money Failsafe sensor life self-diagnostic feature
- Unique sample conditioner
- 4 filter technology incl. water protection filter - easy to access
- Sensor self diagnosis
- Customer field replaceable sensors
- Automatic CO-purge pump
- More than 12 hours operational time with AA rechargeables and optional use of standard AA batteries
- Probe and hose assembly with teflon coating
- Upgradeable: up to 4 sensors
- For measurements: efficiency, true NOx (NO+NO2) and SOX
- Variety of probes for different measurement tasks
- Adapters for temperature and air flow probes
- Optional Peltier-Cooler and solid fuel adapter
- More than 800 complete combustion records
- Infrared communication to Laptop or PC
- Software for computer or Laptop free of charge on our website
- TÜV approved
- EN 50379 Part 2
O2 measurement: | Range:0...21.0 Vol.% Accuracy: 0.3 Vol.% absolut |
CO-measurement (H2-compensated): | Range: 0...4,000 ppm Accuracy: 20 ppm: 0...400 ppm, 5 %f.r..: 400...4.000 ppm |
CO- measurement solid fuel (optional): | Range: 0...32,000 ppm Accuracy: 104 ppm: 0...1,000 ppm, 800 ppm: ...32,000 ppm |
NO- measurement (optional:) | Range: 0...2,000 ppm, continually resilient up to 1,000 ppm Accuracy: 5 ppm: 0...100 ppm, 5 % f.r. |
Ambient Air temperature TA: | Range: 0...257 °F (-20...125°C) Accuracy: .3 °F: 32...122 °F |
Flue Gas temperature measurement TS: | Range: 32...1472 °F Accuracy: EN 50379 |
Chimney Draught: | +/- 16.00" H2O (+/- 40.00 mBar) |
CO2-Calculation: | Range: 0...CO2max Resolution: 0.1 % |
Stack losses-QA: | In reference to selected fuel Resolution: 0.1 %, |
Efficiency - η: | Range: 0...100.0 %, condensation is automatically detected Resolution: 0.1 % |
Automatic CO purge pump: | Dew point calculation in reference to the selected fuel Resolution: 0.2 °F |
Condensate: | readings in kg/m3 (gas) or kg/l (oil) |
Date / time: | realtime clock with backup battery |
Storage temperature: | -4...122 °F |
Work temperature: | 41...104 °F, to meet specifications |
Current supply: | 4 x AA rechargeable batteries or mains supply |
Weight: | ca. 2.87 lb |